WDT410 Series
Cooling Tower Conductivity plus
pH/ORP Controller
Instruction Manual
Five Boynton Road Hopping Brook Park Holliston, MA 01746 USA
TEL: 508-429-1110 FAX: 508-429-7433 WEB: www.walchem.com
W A L C H E M
IWAKI America Inc.
WDT410 Controllers
Vista de página 0
1 2 3 4 5 6 ... 57 58

Resumo do Conteúdo

Página 1 - Instruction Manual

WDT410 Series Cooling Tower Conductivity plus pH/ORP Controller Instruction Manual Five Boynton Road Hopping Broo

Página 2 - Proprietary Material

7 Figure 1 WDT410 Conduit Wiring POWERFEEDBLEEDBIO2CONDUCTIVITYELECTRODEFLOW SWITCH(OPTIONAL)FLOW METER 2(OPTIONAL)4-20mA #2(OPTIONAL)

Página 3

8 Figure 2 Typical Installation HEATEXCHANGERCOOLING TOWERMETERING PUMPSFLOWFLOWSWITCHSAMPLEVALVE1/4" POLYPROPANEL 19" X 24

Página 4 - 1.0 INTRODUCTION

9 Figure 2a Typical Installation Intermittent Sampling TO ELECTRODETO SOLENOIDTOCONSTANT110 VOLTSPE DISCHARGETUBINGCHEMICALPUMPTOSANITARYSE

Página 5 - 2.0 SPECIFICATIONS

10 Figure 2b Typical Installation Submersion Electrode TO110 VOLT ACOUTLETTOSANITARYSEWERCOOLINGTOWEROPENSUMPCIRCULATIONPUMP(X) Unions; insta

Página 6 - 2.3 Mechanical

11 Figure 3 Inputs ConductivityElectrodePower Supply(115 VAC or 230 VAC)Contact Closure:Polarity not criticalReed SwitchFlow MeterPolarity no

Página 7 - Low Limit High Limit

12 Figure 4 Outputs Pump(s)Bleed Solenoid/Motorized Ball ValveAlarmL1 L2/NL2 L2 L2 L2 L2 L2BLEEDN.C.N.O. N.C.BOI 1N.O.N.C.FEEDN.C.BIO 2N.O.

Página 8 - 3.3 Installation

13 4.0 FUNCTION OVERVIEW 4.1 Front Panel Figure 5 Front Panel 4.2 Display A summary screen is displayed while th

Página 9 - CAUTION

14 4.3 Keypad The keypad consists of 4 directional arrow keys and 4 function keys. The arrows are used to move the adjustment cursor and change set

Página 10

15 4.6 Shut Down To shut the controller down, simply turn off the power. Programming remains in memory. It is important that the pH/ORP electrode

Página 11 - 17½"

16 Figure 7 Main Menu 2000 S 67°FConductivity2000 S 5.05pHNORMAL2000 S 67°FTemperature2000 S 67°FpH

Página 12 - INTERMITTENT SAMPLING

Notice © 2014 WALCHEM, Iwaki America Inc. (hereinafter “Walchem”) 5 Boynton Road, Holliston, MA 01746 USA (508) 429-1110 All Rights Reserved Prin

Página 13 - SUBMERSION ELECTRODE

17 5.2 Conductivity Menu The conductivity menu provides the following settings: Calibration, Self Test, Unit selection, and sampling mode setup.

Página 14 - Figure 3 Inputs

18 Figure 8 Conductivity Menu Calibrate Cond2000 S/cmCond Self Test1000 S/cmCond Self Test 666 ppmUnits S/cmS/cmUnits

Página 15 - Recorder

19 5.3 Temperature Menu The Temperature menu contains the following settings: Calibration and Units (if the Temp element is detected when the unit

Página 16 - 4.0 FUNCTION OVERVIEW

20 5.4 pH/ORP Input Menu Cal'd Displays the date of the last electrode calibration. 2 Pt Calibration for pH electrodes Press the ENTER key t

Página 17 - Initial Startup

21 Cal'd Press the ENTER key to perform a 2 point calibration of the electrode. If using manual temperature compensation, the first display wi

Página 18 - 5.0 OPERATION

22 1 Pt Calibration for ORP electrodes Rinse Electrode Remove the electrode from the process and rinse it off. Press ENTER to go to the next step.

Página 19 - Operation

23 Figure 10 pH/ORP Input Menu

Página 20 - Intermittent

24 5.5 Bleed Menu The Bleed Menu provides the following settings: Set Point, Dead Band, Control Direction, HOA. The Bleed menu will be indicated o

Página 21

25 Figure 11 Bleed Menu 2000 S 68° FBleed 1:01:15Bleed 1:01:15Set Point 2000Bleed 1:01:15Dead Band 20

Página 22 - Temperature Menu

26 5.6 Feed Menu The Feed Menu adapts to the selected Feed output mode. Hint: For easiest programming, program Feed Mode first, then step through

Página 23

TABLE OF CONTENTS 1.0 INTRODUCTION ...

Página 24 - 1 Pt Calibration for

27 Feed Based on Water Contactor Mode Time/Cont. (Time per contact.) This determines the length of time that the feed pump should be on for each

Página 25

28 Figure 12 Feed Menu 2112Feed Chem Feed ModeTIMEOUTFeed TIMEOUTHAND OFF >AUTO2000 S/cm 68° FFeed 21:05

Página 26 - Figure 10 pH/ORP Input Menu

29 5.7 WM1 and WM2 Menus The Water Meter 1 and 2 menus are used to set up the type of meter and how to convert the water meter signal into volume

Página 27

30 5.8 pH/ORP Control Menu The pH/ORP Control Menu provides the following independent settings: Set Point, Dead Band, Time Limit, Control Directi

Página 28

31 Figure 14 pH/ORP Control Menu

Página 29

32 5.9 Bio1 and Bio2 Menus The Bio 1 and Bio 2 menus are separate from each other but operate in exactly the same way. Each menu provides the fol

Página 30

33 Prog Bio 1 Add Press ENTER here to see a list of all of the biocide adds presently scheduled. The first screen displayed is for Today's Bi

Página 31

34 Figure 15 Biocide 1 Menu

Página 32 - WM1 and WM2 Menus

35 Figure 16 Biocide 2 Menu

Página 33

36 5.10 Time Menu This menu has only one choice, to set the Time used for Biocide adds or Datalogs. This menu will appear as follows: Time: 2Mon

Página 34

1 1.0 INTRODUCTION The Walchem WDT410 Series controllers offer conductivity and watermeter-based control of cooling tower water, control of corro

Página 35 - 5.9 Bio1 and Bio2 Menus

37 5.11 Cond Alarm Menu The Cond Alarm menu screen will appear as follows: Cond Alrm OFF Cond Alrm LOW ALRM Cond Alrm HI ALRM

Página 36

38 5.12 pH/ORP Alarm Menu The pH Alarm menu screen will appear as follows: pH Alrm OFF pH Alrm LOW ALRM pH Alrm HI ALRM Low A

Página 37 - Figure 15 Biocide 1 Menu

39 5.13 4-20mA Menu (Optional) This menu is only available if the optional 4-20mA output board(s) is (are) installed in the controller. This men

Página 38 - Figure 16 Biocide 2 Menu

40 5.14 pH/ORP 4-20mA Menu (Optional) This menu will only appear if the optional 4-20mA output board is installed on the pH input board. It is

Página 39 - Set Time

41 5.15 Access Code Menu This menu determines whether the access code feature of the controller is enabled or disabled and allows you to customiz

Página 40 - Cond Alarm Menu

42 5.16 Datalog Menu This menu is available if the data logging option has been purchased. This is indicated in the model code by the letter U at t

Página 41 - Possible status screens

43 Figure 23 Datalog Menu DatalogCurrent DatalogDatalogCopy Event LogDatalog MenuENTER EXIT 67° FDatalog2000 µSDatalogTransfer Suc

Página 42

44 5.17 Config Menu This menu allows you to export a file that contains all of the set points in the controller to a USB flash disk drive, and then

Página 43 - Fixed 20 mA Out

45 5.18 Upgrade Menu This menu is used to upgrade the software to a newer version. It is used to upgrade the software to a newer version. If a new

Página 44 - New Value

46 6.0 MAINTENANCE The WDT controller itself requires very little maintenance. Wipe with a damp cloth. Do not spray down the controller unless the

Página 45

2 2.0 SPECIFICATIONS 2.1 Measurement Performance Conductivity Range 0 - 10,000 µS/cm (microSiemens/centimeter) Conductivity Resolution 1 µS/

Página 46 - Datalog Menu

47 6.2 Replacing the Fuses CAUTION: Disconnect power to the controller before opening front panel! Locate the fuses on the circuit board at the

Página 47 - Import Config

48 LOW ALARM The summary screen will display an L at the left end of the bar graph and the alarm relay will trip. The controller will continue to c

Página 48 - Upgrade

49 BLEED TIMEOUT This error condition will stop conductivity control. It is caused by the bleed output being activated for longer than the programm

Página 49 - 6.0 MAINTENANCE

50 pH HIGH ALARM This error message indicates that the pH is above the programmed pH High Alarm value. The pH will continue to be monitored, and th

Página 50 - 7.0 TROUBLESHOOTING

51 7.2 Conductivity Readout Does Not Change If the readout is stuck at or near zero: Possible Causes Corrective Action Dry electrode Check for

Página 51 - COND ERROR

52 7.5 Procedure for checking relay outputs If any prewired output is not activating the device (pump, valve, etc.) attached to it: If the relay

Página 52 - Possible Cause

53 8.0 SERVICE POLICY The WDT410 series Cooling Tower Controller has a 2-year warranty on electronic components and a 1-year warranty on mechanic

Página 53

WDT410 VOLTAGE 1 = 120 VAC, prewired 5 = 100-240 VAC, conduit OUTPUT N = No data output 4 = Single 4-20 mA output 2 = Dual 4

Página 54

FIVE BOYNTON ROAD HOPPING BROOK PARK HOLLISTON,

Página 55

3 2.3 Mechanical Enclosure Material Polycarbonate NEMA Rating NEMA 4X Dimensions 8.5" x 6.5" x 5.5" Display 2 x 16 character bac

Página 56 - 8.0 SERVICE POLICY

4 WDT Variables and their Limits (continued) Biocide Menus Low Limit High Limit Pre-Bleed 1 µS/cm 9,999 µS/cm (0 disables pre-bleed) Lock

Página 57 - Model Code

5 3.0 UNPACKING & INSTALLATION 3.1 Unpacking the unit Inspect the contents of the carton. Please notify the carrier immediately if there a

Página 58

6 3.4 Icon Definitions Symbol Publication Description IEC 417, No.5019 Protective Conductor Terminal IEC 417, No. 5007 On (Supply) IEC 417,